Upstream Network
Sks=1453 MVA
V=154 kV
Ankara Balgat TM
Zı=(0,0069+j.0,0681) pu
Zo=(0,0069+j.0,1363) pu
Str = 40 MVA
%Uk =11,7
Zı =(0+j.0,1462) pu
Zo =(0+j.0,1462) pu
2 Unit
3(1x240)
I3f=6,803kA
Ift=0,455kA
114 m
1 Circuit
zı=(0,0004+j. 0,0011) pu
zo=(0,0036+j.0,0044) pu
3(1x240)
1 🗲
114 m
1 Circuit
3(1x240)
2 🗲
I3f=5,124kA
Ift=0,438kA
3610 m
1 Circuit
zı=(0,0271+j.0,0686) pu
zo=(0,2168+j.0,2744) pu
3(1x240)
3 🗲
I3f=4,522kA
Ift=0,43kA
1923 m
1Circuit
zı=(0,0144+j.0,0365) pu
zo=(0,1152+j.0,146) pu
3(1x240)
4 🗲
I3f=4,16kA
Ift=0,423kA
1415 m
1 Circuit
zı=(0,0106+j. 0,0269) pu
z0=(0,0848+j.0,1076) pu
3x477 MCM
🗲 5
I3f=3,527kA
Ift=0,426kA
6236m
1 Circuit
zı=(0,075+j.0,192) pu
z0=(0,225+j.0,6144) pu
3x477 MCM
🗲 6
I3f=2,595kA
Ift=0,404kA
4571 m
1 Circuit
zı=(0,055+j.0,1407) pu
z0=(0,205+j.0,4502) pu
3x477 MCM
🗲 7
I3f=2,243kA
Ift=0,39kA
2698 m
1Circuit
zı=(0,0325+j.0,0831) pu
z0=(0,1825+j.0,2659) pu
400 V
🗲 8
I3f=28,19kA
Ift=18,35kA
Str1 = 1600 kVA
%Uk1 = 11,7
400 V
Str2 = 1600 kVA
%Uk2 = 11,7
🗲 9
I3f=26,3kA
Ift=17,32kA
Resistance =61 Ω
Zo =(3,0738+j.0) pu
31,5 kV
İ.M
DM 1
DM 5
DM 6
DM 7
DM 2
DM 3
DM 4
*In the calculation of
reactance values: HV underground cables are single and laid underground at 7 cm
distance, and in overhead lines, flatcross arm and dm = 1.1 m are taken.
Calculations Based on 100 (Per Unit
Method):
Upstream Network :Z Upstream
Network =100/Sk
pu , X Upstream
Network =0,98.Z Upstream
Network
, R Upstream
Network =0,1.X Upstream
Network
Tranformer : Xtr= Uk /S
pu
Conductor: Rh= R.L.100/Vn2
pu
1-Short Circuit at Point
DM.1
:
-Three Phase
Short Circuit Calculations :
X1 (1)=Xs +Xtr (1)+Xh1 (1)
=0,0681+0,1462+0,0011=0,2154
pu
R1 (1)=Rs +Rtr (1)+Rh1 (1)
=0,0069+0+0,0004=0,0073
pu
Z1 (1)=R1 (1)+j X1 (1)
=0,0073+ j 0,2154=0,2155
pu
Ik3 ''=6,803
kA
-Phase Ground short circuit
calculations
X0 (1)=Xs0 +Xtr0 (1)+Xh0 (1)
=0,1363+0,1462+0,0044=0,2869
pu
R0 (1)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)
=0,0069+0+9,2214+0,0036=9,2319
pu
Z0 (1)=R0 (1)+j X0 (1)
=9,2319+ j 0,2869=9,2364
pu
Z0 (1)/Z1 (1)
=9,2364/0,2155= 42,86 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 6,803 x
3
= 0,455
kA
2+ Z 0
2+ 42,86
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
-Peak
Asymmetrical Current Calculations
IEC 60909
standardına göre tepe akımı:
k1 =1,02+0,98 e(-3R/x) = 1,91
Ip1 = k.√2 .
Ik3 '' =18,376
kA
-Thermal Short Circuit Current
At a point far from
the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,106
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 6,803
Breaker Power : Sksc = √3.Un.1,1. Ik3 '' = √3.36.1,1.6,803=
467
MVA
2-Short Circuit at
Point
DM.2 :
-Three Phase
Short Circuit Calculations :
X1 (2)=Xs +Xtr (1)+Xh1 (1)+Xh1 (2)=0,0681+0,1462+0,0011+0,0686=0,284
pu
R1 (2)=Rs +Rtr (1)+Rh1 (1)+Rh1 (2)
=0,0069+0+0,0004+0,0271=0,0344
pu
Z1 (2)=R1 (2)+j X1 (2)
=0,0344+ j 0,284=0,2861
pu
Ik3 ''=5,124
kA
-Phase Ground short circuit
calculations
X0 (2)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (2)
=0,1363+0,1462+0,0044+0,2744=0,5613
pu
R0 (2)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (2)
=0,0069+0+9,2214+0,0036+0,2168=9,4487
pu
Z0 (2)=R0 (2)+j X0 (2)
=9,4487+ j 0,5613=9,4654
pu
Z0 (2)/Z1 (2)
=9,4654/0,2861= 33,08 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 5,124 x
3
= 0,438
kA
2+ Z 0
2+ 33,08
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
- Peak
Asymmetrical Current Calculations
IEC 60909
standardına göre tepe akımı:
k2 =1,02+0,98 e(-3R/x) = 1,7
Ip2 = k.√2 .
Ik3 '' =12,319
kA
- Thermal
Short Circuit Current
At a point far from the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,028
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 5,124
Breaker Power : Sksc =√3.Un.1,1. Ik3 '' = √3.36.1,1.5,124=
351
MVA
3-Short Circuit at Point
DM.3 :
-Three Phase
Short Circuit Calculations :
X1 (3)=Xs +Xtr (1)+Xh1 (1)+Xh1 (2)+Xh1 (3)=0,0681+0,1462+0,0011+0,0686+0,0365=0,3205
pu
R1 (3)=Rs +Rtr (1)+Rh1 (1)+Rh1 (2)+Rh1 (3)
=0,0069+0+0,0004+0,0271+0,0144=0,0488
pu
Z1 (3)=R1 (3)+j X1 (3)
=0,0488+ j 0,3205=0,3242
pu
Ik3 ''=4,522
kA
-Phase Ground short circuit
calculations
X0 (3)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (2)+Xh0 (3)=0,1363+0,1462+0,0044+0,2744+0,146=0,7073
pu
R0 (3)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (2)
+Rh0 (3)
=0,0069+0+9,2214+0,0036+0,2168+0,1152=9,5639
pu
Z0 (3)=R0 (3)+j X0 (3)
=9,5639+ j 0,7073=9,59
pu
Z0 (3)/Z1 (3)
=9,59/0,3242= 29,58 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 4,522 x
3
= 0,43
kA
2+ Z 0
2+ 29,58
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
-Peak
Asymmetrical Current Calculations
Peak current according to IEC 60909
standard:
k3 =1,02+0,98 e(-3R/x) = 1,64
Ip3 = k.√2 .
Ik3 '' =10,488
kA
-Thermal Short Circuit Current
At a point far from
the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,0224
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 4,522
Breaker Power : Sksc = √3.Un.1,1. Ik3 '' = √3.36.1,1.4,522=
310
MVA
4-Short Circuit at Point
DM.4 :
-Three Phase
Short Circuit Calculations :
X1 (4)=Xs +Xtr (1)+Xh1 (1)+Xh1 (2)+Xh1 (3)+Xh1 (4)=0,0681+0,1462+0,0011+0,0686+0,0365++0,0269=0,3474
pu
R1 (4)=Rs +Rtr (1)+Rh1 (1)+Rh1 (2)+Rh1 (3)+Rh1 (4)
=0,0069+0+0,0004+0,0271+0,0144+0,0106=0,0594
pu
Z1 (4)=R1 (4)+j X1 (4)
=0,0594+ j 0,3474=0,3524
pu
Ik3 ''=4,16
kA
-Phase Ground short circuit
calculations
X0 (4)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (2)+Xh0 (3)+Xh0 (4)=0,1363+0,1462+0,0044+0,2744+0,146+0,1076=0,8149
pu
R0 (4)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (2)
+Rh0 (3)+Rh0 (4)
=0,0069+0+9,2214+0,0036+0,2168+0,1152+0,0848=9,6487
pu
Z0 (4)=R0 (4)+j X0 (4)
=9,6487+ j 0,8149=9,6831
pu
Z0 (3)/Z1 (3)
=9,6831/0,3524= 27,48 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 4,522 x
3
= 0,423
kA
2+ Z 0
2+ 27,48
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
-Peak
Asymmetrical Current Calculations
Peak current according to IEC 60909
standard:
k4 =1,02+0,98 e(-3R/x) = 1,61
Ip4 = k.√2 .
Ik3 '' =9,472
kA
-Thermal Short Circuit Current
At a point far from
the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,0202
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 4,16
Breaker Power : Sksc = √3.Un.1,1. Ik3 '' = √3.36.1,1.4,16=
285
MVA
5-Short Circuit at Point
DM.5 :
-Three Phase
Short Circuit Calculations :
X1 (5)=Xs +Xtr (1)+Xh1 (1)+Xh1 (5)=0,0681+0,1462+0,0011+0,192=0,4074
pu
R1 (5)=Rs +Rtr (1)+Rh1 (1)+Rh1 (5)
=0,0069+0+0,0004+0,075=0,0823
pu
Z1 (5)=R1 (5)+j X1 (5)
=0,0823+ j 0,4074=0,4156
pu
Ik3 ''=3,527
kA
-Phase Ground short circuit
calculations
X0 (5)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (5)=0,1363+0,1462+0,0044+0,6144=0,9013
pu
R0 (5)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (5)
=0,0069+0+9,2214+0,0036+0,225=9,4569
pu
Z0 (5)=R0 (5)+j X0 (5)
=9,4569+ j 0,9013=9,4998
pu
Z0 (5)/Z1 (5)
=9,4998/0,4156= 22,86 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 4,522 x
3
= 0,426
kA
2+ Z 0
2+ 22,86
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
-Peak
Asymmetrical Current Calculations
Peak current according to IEC 60909
standard:
k5 =1,02+0,98 e(-3R/x) = 1,55
Ip5 = k.√2 .
Ik3 '' =7,731
kA
-Thermal Short Circuit Current
At a point far from
the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,0167
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 3,527
Breaker Power: Sksc = √3.Un.1,1. Ik3 '' = √3.36.1,1.3,527=
242
MVA
6-Short Circuit at Point
DM.6 :
-Three Phase
Short Circuit Calculations :
X1 (6)=Xs +Xtr (1)+Xh1 (1)+Xh1 (5)+Xh1 (6)=0,0681+0,1462+0,0011+0,192+0,1407=0,5481
pu
R1 (6)=Rs +Rtr (1)+Rh1 (1)+Rh1 (5)+Rh1 (6)
=0,0069+0+0,0004+0,075+0,055=0,1373
pu
Z1 (6)=R1 (6)+j X1 (6)
=0,1373+ j 0,5481=0,565
pu
Ik3 ''=2,595
kA
-Phase Ground short circuit
calculations
X0 (6)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (5)+Xh0 (6)=0,1363+0,1462+0,0044+0,6144+0,4502=1,3515
pu
R0 (6)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (5)+Rh0 (6)
=0,0069+0+9,2214+0,0036+0,225+0,205=9,6619
pu
Z0 (6)=R0 (6)+j X0 (6)
=9,6619+ j 1,3515=9,756
pu
Z0 (6)/Z1 (6)
=9,756/0,565= 17,27 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 4,522 x
3
= 0,404
kA
2+ Z 0
2+ 17,27
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
-Peak
Asymmetrical Current Calculations
Peak current according to IEC 60909
standard:
k5 =1,02+0,98 e(-3R/x) = 1,48
Ip5 = k.√2 .
Ik3 '' =5,431
kA
-Thermal Short Circuit Current
At a point far from
the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,0136
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 2,595
Breaker Power : Sksc = √3.Un.1,1. Ik3 '' = √3.36.1,1.2,595=
178
MVA
7-Short Circuit at Point
DM.7 :
-Three Phase
Short Circuit Calculations :
X1 (7)=Xs +Xtr (1)+Xh1 (1)+Xh1 (5)+Xh1 (6)+Xh1 (7)=0,0681+0,1462+0,0011+0,192+0,1407+0,0831=0,6312
pu
R1 (7)=Rs +Rtr (1)+Rh1 (1)+Rh1 (5)+Rh1 (6)+Rh1 (7)=0,0069+0+0,0004+0,075+0,055+0,0325=0,1698
pu
Z1 (7)=R1 (7)+j X1 (7)
=0,1698+ j 0,6312=0,6536
pu
Ik3 ''=2,243
kA
-Phase Ground short circuit
calculations
X0 (7)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (5)+Xh0 (6)+Xh0 (7)=0,1363+0,1462+0,0044+0,6144+0,4502+0,2659=1,6174
pu
R0 (7)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (5)+Rh0 (6)+Rh0 (7)
=0,0069+0+9,2214+0,0036+0,225+0,205++0,1825=9,8444
pu
Z0 (7)=R0 (7)+j X0 (7)
=9,8444+ j 1,6174=9,9764
pu
Z0 (7)/Z1 (7)
=9,9764/0,6536= 15,26 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 4,522 x
3
= 0,39
kA
2+ Z 0
2+ 15,26
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
-Peak
Asymmetrical Current Calculations
Peak current according to IEC 60909
standard:
k5 =1,02+0,98 e(-3R/x) = 1,46
Ip5 = k.√2 .
Ik3 '' =4,631
kA
-Thermal Short Circuit Current
At a point far from
the generator
Ik3 ''/Ik3 =1 and n=1
m =
1
[ e4.f.Tk.ln(K-1) -1]= 0,0129
2.f.Tk.Ln(K-1)
Ith =Ik3 ''.√(m+n)
= 2,595
Breaker Power: Sksc = √3.Un.1,1. Ik3 '' = √3.36.1,1.2,243=
154
MVA
Short Circuit at Point
8. Str1 LV side Short circuit :
-Three Phase
Short Circuit Calculations :
X1 (8)=Xs +Xtr (1)+Xh1 (1)+Xh1 (2)+Xh1 (3)+Xh1 (4)+Xstr (1)=0,0681+0,1462+0,0011+0,0686+0,0365+0,0269+3,75=4,0974
pu
R1 (8)=Rs +Rtr (1)+Rh1 (1)+Rh1 (2)+Rh1 (3)+Rh1 (4)+Rh1 (5)+ Rstr (1)
=0,0069+0+0,0004+0,0271+0,0144+0,0106+0=0,0594
pu
Z1 (8)=R1 (8)+j X1 (8)
=0,0594+ j 4,0974=4,0978
pu
Ik3 ''=0,358
kA
LV Side
Three Phase Short Circuit
: Ik3AG ''= Ik3 ''. Vp /Vs
= 28,19 kA
-Phase Ground short circuit
calculations
X0 (8)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (2)+Xh0 (3)+Xh0 (4)+Xstr10 (1)=0,1363+0,1462+0,0044+0,2744+0,146+0,1076+3,75=4,5649
pu
R0 (8)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (2)
+Rh0 (3)+Rh0 (4)+ Rstr10 (1)
=0,0069+0+9,2214+0,0036+0,2168+0,1152+0,0848+0=9,6487
pu
Z0 (8)=R0 (8)+j X0 (8)
=9,6487+ j 4,5649=10,6741
pu
Z0 (8)/Z1 (8)
=10,6741/4,0978= 2,6 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 0,358 x
3
= 0,233
kA
2+ Z 0
2+ 2,6
Z 1
Three phase short circuit current is greater than phase-to-ground short circuit current
LV Side Phase
Ground Short Circuit
: Ik1fAG ''= Ik1f ''. Vp /Vs
= 18,35 kA
Short Circuit at Point
9. Str2 LV side Short circuit :
-Three Phase
Short Circuit Calculations :
X1 (9)=Xs +Xtr (1)+Xh1 (1)+Xh1 (5)+Xh1 (6)+Xh1 (7)+Xstr (1)=0,0681+0,1462+0,0011+0,192+0,1407+0,0831+3,75=4,3812
pu
R1 (9)=Rs +Rtr (1)+Rh1 (1)+Rh1 (5)+Rh1 (6)+Rh1 (7)+Rstr (1)=0,0069+0+0,0004+0,075+0,055+0,0325+0=0,1698
pu
Z1 (9)=R1 (9)+j X1 (9)
=0,1698+ j 4,3812=4,3845
pu
Ik3 ''=0,334
kA
LV Side Three
Phase Short Circuit
: Ik3AG ''= Ik3 ''. Vp /Vs
= 26,3 kA
-Phase Ground short circuit
calculations
X0 (9)=Xs0 +Xtr0 (1)+Xh0 (1)+Xh0 (5)+Xh0 (6)+Xh0 (7)+Xstr0 (1)=0,1363+0,1462+0,0044+0,6144+0,4502+0,2659+3,75=5,3674
pu
R0 (9)=Rs0 +Rtr0 (1)+3.Rn+Rh0 (1)+Rh0 (5)+Rh0 (6)+Rh0 (7)+Rstr0 (1)
=0,0069+0+9,2214+0,0036+0,225+0,205+0,1825+0=9,8444
pu
Z0 (9)=R0 (9)+j X0 (9)
=9,8444+ j 5,3674=11,2125
pu
Z0 (9)/Z1 (7)
=11,2125/4,3845= 2,56 > 1 the phase-to-ground short circuit current is greater than the two phase-to-ground fault currents.
Ik1t ''=
Ik3 ''x 3
= 0,334 x
3
= 0,22
kA
2+ Z 0
2+ 2,56
Z 1
LV Side Phase
Ground Short Circuit: Ik1fAG ''= Ik1f ''. Vp /Vs
= 17,32 kA