Cable Voltage Drop-Loss Calculation
Tranformer LV Panel.
LV Line
LV Pole Selection
LV Pole Vector Calculations
LV Tension Calculation
LV(All Ice Zone)Conductor tension
LV Conductor System Tension
(LV+1.4375xHV) Transformer Pole
LV Conductor Parameter Ice-Wind Load
HV&LV Pole
HV&LV Common(Joint) Pole Calculations
HV&LV Common Pole Vector Calculations
HV&LV Overhead Line Tension
HV&LV Conductor (All Ice Zone) Tension
(HV+0.81xLV) Conductor System Tension
(LV+1.4375xHV) Transformer Pole
HV&LV Conductor Parameter Ice-Wind Load
HV Line
HV Line Parameter Ice Load-Wind Tension
Overhead Line ag, aw, ar, Profile
ENH ag,aw,ar, Mesafe,Açı Hesapları
Overhead Line ag, aw, ar, angle and distance
OHL Up Lift Control
Conductor Pulling: Sag-Tension Animation
Conductor Pulling:Temp-Wind Based Tension
Conductor Tensinsion-Sag Calculation(Project)
Conductor State Change Equation
HV Distribution Line Tension Table
HV Overhead Line Hawk(2x477)
HV Overhead Line Pigeon(3x3/0)
Grounding&Earthing
Earthing Type Calculation
Inside Building Earth Measurement
Topraklama İletkeni Kesit Hesabı
Column/Neutral/Underground Cable Cross-Section Calculation
Touch-StepVoltage,Mesh Grounding Calculation
Short Circuit Current Calculations
Cable Cross-Section Calculation
Other
Ataturk's Memories
Numerology(Ebced)
Places to Visit: Caravan Campgrounds
Apartment Management Program
2
kiþi Online
[
Home Page
]
Underground Cable Selection and Voltage Drop Calculations
Cos φ =
φ = 30,68
Secondary Voltage
:
Soil Temperature
(k1):
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Nature of Soil
(k2):
Very Wet Soil
Wet Soil
Damp Soil
Dry Soil
Very Dry Soil
Laying Depth
(k3):
0,5
0,6
0,8
1
1,2
1,5
1,75
2
2,5
3
m
Impedance
Cu 56 Al 35
pvc
xlp
Laying Cables in Underground Trenches:
xlpe
pvc
Earth Temp Derating Factor
(K1):
0,96
0,95
Nature of Soil Derating Factor
(K2):
1
1
Earth Laying Depth Rating Factor
(K3):
0,96
0,96
Underground Cable Output Power(kW):
kW
A
A
Cable Length(m):
Number of Circuits(Number):
Copper
Aluminium
Selected Cross-Section(pvc)
:
3x70+35 ( 176 / 193 A)
3x120+70 (192 / 210 A )
Active Voltage Drop
Δu.
aktive:
8,26
7,71
Active Voltage Drop Ratio
%Δu.
aktive:
2,17
2,03
Reactive Voltage Drop
Δu.
reactive:
1,42
1,37
Reactive Voltage Drop Ratio
%Δu.
reactive:
0,37
0,36
Total Voltage Drop Rate
%e
total:
2,54
2,39
Cable Fuse:
160 A
200 A
Click here for detailed analysis and report.